NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
3 Installation Guide
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
79
Table 3-13
DIP switch setting on a T/H sensor
Locati
on
Display Name Addr
ess
DIP Switch Sequence No.
1
2
3
4
5
6
Air
return
side
Return-air 2
temp/humid
1
ON
OFF
OFF
OFF
OFF
OFF
Cold
aisle
Cold-aisle 1
temp/humid
11
ON
ON
OFF
ON
OFF
OFF
Cold-aisle 2
temp/humid
12
OFF
OFF
ON
ON
OFF
OFF
Cold-aisle 3
temp/humid
13
ON
OFF
ON
ON
OFF
OFF
Cold-aisle 4
temp/humid
14
OFF
ON
ON
ON
OFF
OFF
Cold-aisle 5
temp/humid
15
ON
ON
ON
ON
OFF
OFF
Hot
aisle
Hot-aisle 1
temp/humid
21
ON
OFF
ON
OFF
ON
OFF
Hot-aisle 2
temp/humid
22
OFF
ON
ON
OFF
ON
OFF
Hot-aisle 3
temp/humid
23
ON
ON
ON
OFF
ON
OFF
Hot-aisle 4
temp/humid
24
OFF
OFF
OFF
ON
ON
OFF
Hot-aisle 5
temp/humid
25
ON
OFF
OFF
ON
ON
OFF
The default addresses of T/H sensors purchased from Huawei are 1.
Keep the last RS485_R toggle switch at OFF.
After the addresses are set, power on the device. On the display's home screen, choose
Settings
>
System Settings
>
T/H Sensor
, and set the sensors in the aisles corresponding
to the addresses to
Enable
. Otherwise, the sensors will not work.
----End
Содержание NetCol5000-A
Страница 264: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 265: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 266: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 267: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...