5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
185
Step 5
Install the new condensate pump and reinstall the condensate pump assembly in the cabinet.
Connect the water pipe and secure it using hose clamps. Connect the condensate pump power
cable.
Figure 5-34
Installing a condensate pump
Step 6
Remove the blockage from the pipe and close the front door.
Step 7
Power on the device. On the LCD home screen, choose
Maint
>
Performance Maint
, and
clear the condensate pump runtime.
Figure 5-35
Performance maintenance
Step 8
Tap
Startup
on the home screen. Ensure that the air conditioner is running normally without
any alarms.
----End