NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
3 Installation Guide
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
51
Procedure
Step 1
Remove the bonnet of the low-pressure needle valve shown in
pressure gauge leather hose to the needle valve.
Figure 3-25
Exhausting nitrogen
(1) Low-pressure needle
valve
(2) Exhaust pipe needle
valve
(3) Liquid pipe needle valve
Step 2
Open the pressure gauge valve. Loud noises of air flow are generated at first and then
disappear gradually.
Step 3
After the air is exhausted, remove the pressure gauge and install the valve bonnet.
Step 4
Continue exhausting nitrogen from the exhaust pipe needle valve and liquid pipe needle valve
by performing
----End