Alarm
ID
Alarm
Alarm
Severity
Impact
Possible Cause
Solution
3.
The fan is faulty.
a145 handling methods.
2.
Cut off the three-phase
power supply and check
whether the driver output
cable is faulty. See the
a145 handling methods.
3.
Replace the fan.
a159
Outdoor
fan Dr.
sampling
drift
Major
The alarm
is
generated.
The sampling circuit is
faulty.
Replace the fan driver.
a160
Outdoor
fan Dr OP
ground
fault
Major
The alarm
is
generated.
The driver output cable is
short-circuited or grounded.
Cut off the three-phase
power supply and check
whether the driver output
cable is faulty or grounded.
a161
Outdoor
fan output
current
Imba
Major
The alarm
is
generated.
The fan three-phase loads are
imbalanced.
Check whether the fan is
faulty.
a162
Outdoor
fan pres
sensor
fault
Warning
The alarm
is
generated.
1.
A cable of the pressure
sensor is loose.
2.
The pressure sensor is
faulty.
1.
Secure the pressure
sensor terminals.
2.
Replace the press sensor.
a163
Outdoor
fan
overtemp
Major
The alarm
is
generated.
1.
The fan overtemperature
feedback cable is loose.
2.
The outdoor unit is dirty
and blocked.
3.
The fan is faulty.
1.
Secure the cable
connected to the fan
overtemperature feedback
terminal.
2.
Clean the fan and remove
obstacles to ensure that
the fan works properly.
3.
Replace the fan.
a164
Outdoor
fan Dr
Elec
control
box HT
Warning
The alarm
is
generated.
Honeycomb holes in the
driver rear panel are dirty or
blocked.
Clean the honeycomb holes
using a brush.
a165
Outdoor
fan power
freq error
Major
The alarm
is
generated.
The power grid freq is
abnormal.
Power off the driver and
verify that the supply freq
meets specifications.
a166
Outdoor
fan driver
fault
Major
The alarm
is
generated,
and the
compresso
r shuts
down.
The fan driver has generated
a major alarm.
Clear the major alarm for the
driver.
Содержание NetCol5000-A
Страница 264: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 265: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 266: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 267: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...