NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
C Parameter Description
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
250
Menu
Parameter
Description
Default Value
set to
Client
.
Network port
It is recommended that you retain the default
value 16100. If you need to change the value,
enter a value as required. This parameter is
configurable when
Link mode
is set to
Client
.
16100
Settings
>
Comm
Settings
>
SNMP Settings
4.5.7 Setting Communications Parameters (SNMP Parameters)
Settings
>
Alarm Settings
Action
Three options are available for setting
whether to report an alarm.
Enable
: Alarms are reported to the EMS.
The LCD displays active alarms and the
system implements related protection
actions.
Disable
: Alarms are not reported and no
protection actions are implemented.
Allow
Delay
Specifies the delay time for reporting alarms.
Not displayed
Threshold
Specifies the alarm threshold for a certain
alarm.
Not displayed
Settings
>
System
Settings
>
COMM Settings
T/H control type
Cold-aisle
,
Hot-aisle
,
Return-air
, or
Supply-air
can be set as required. The
temperature and humidity set points
correspond to the selected control type can be
set.
Return-air
Ctrl temp setpoint
at ctrl point
After the T/H control type and the
temperature value under this type are set, the
device conducts cooling or heating based on
the settings.
23.0°C
Ctrl humid
setpoint at ctrl
point
After the T/H control type and the humidity
value under this type are set, the device
conducts humidifying or dehumidifying based
on the settings.
50.0%RH
Cold-aisle sensor
The sensors in cold aisles can be set to
Enable
or
Disable
.
Disable
Hot-aisle sensor
The sensors in hot aisles can be set to
Enable
or
Disable
.
Disable
Heat
Enable
indicates that the electric heater will
be started when the ambient temperature is
lower than the certain temperature range of
the temperature set point.
Disable
indicates
that the electric heater will not be started.
Enabled when active pwr
indicates that the
electric heater will be started when the main
Enable
Содержание NetCol5000-A
Страница 264: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 265: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 266: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 267: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...