NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
191
Figure 5-40
Install a wet film humidifier
Put the bottom of wet film humidifier into the installation position, and then put the top into the
installation position. Fasten the two captive nuts.
Step 5
Install the air filter and close the rear door.
Step 6
Power on the device. On the LCD home screen, choose
Maint
>
Performance Maint
, and
clear the humidifier runtime.
Figure 5-41
Performance maintenance
Step 7
Tap
Startup
on the home screen. Ensure that the air conditioner is running normally without
any alarms.
----End