NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
139
Alarm
ID
Alarm
Alarm
Severity
Impact
Possible Cause
Solution
a049
Supply-air
LT
Warning
The alarm
is
generated.
1.
The load is low.
2.
The ambient temp is low.
3.
The supply-air LT alarm
threshold is
inappropriate.
4.
The temp displayed is
different from the actual
temp.
5.
The air filters are
blocked.
1.
Please consult Huawei
technical support.
2.
Check other causes if the
alarm persists after
startup.
3.
Adjust the supply-air LT
alarm threshold.
4.
Calibrate or replace the
abnormal sensors.
5.
Maintain or replace the
air filters.
a050
Cold-aisle
HT
Critical
The alarm
is
generated,
and the
rotational
speed of
the
compresso
r
increases.
1.
The T/H sensors are
located in inappropriate
position.
2.
The load is high or the
refrigeration capacity is
insufficient.
3.
The ambient temp is
high.
4.
The cold-aisle HT alarm
threshold is
inappropriate.
5.
The temp displayed is
different from the actual
temp.
1.
Adjust the position of the
T/H sensors.
2.
Add more air conditioner
units or Consult
Huawei technical
support.
3.
Check other causes if the
alarm persists after
startup.
4.
Adjust the cold-aisle HT
alarm threshold.
5.
Calibrate or replace the
abnormal sensors.
a051
Hot-aisle
HT
Critical
The alarm
is
generated.
1.
The T/H sensors are
located in inappropriate
position.
2.
The load is high or the
refrigeration capacity is
insufficient.
3.
The ambient temp is
high.
4.
The hot-aisle HT alarm
threshold is
inappropriate.
5.
The temp displayed is
different from the actual
temp.
1.
Adjust the position of the
T/H sensors.
2.
Add more air conditioner
units or Consult
Huawei technical
support.
3.
Check other causes if the
alarm persists after
startup.
4.
Adjust the hot-aisle HT
alarm threshold.
5.
Calibrate or replace the
abnormal sensors.
a052
Supply-air
1 temp
invalid
Supply-air
2 temp
invalid
Major
The alarm
is
generated.
1.
The cables to the T/H
sensor are loose or
damaged
2.
The T/H sensor is faulty.
1.
Remove dirt or water
from the T/H sensor.
2.
Maintain or replace the
T/H sensor.
a053
PSU 1
fault
Major
The alarm
is
The PSU is faulty.
Maintain or replace the PSU.
Содержание NetCol5000-A
Страница 264: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 265: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 266: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 267: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...