NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
4 Commissioning
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
95
Parameter
Description
Configuration Principle
recommended
Ctrl humid
setpoint at
ctrl point
After the T/H control type and
the humidity value under this
type are set, the device
conducts humidifying or
dehumidifying based on the
settings.
Set this parameter as required.40%–60%
RH recommended
Cold-aisle
sensor
The sensors in cold aisles can
be set to
Enable
or
Disable
.
Enable
the corresponding humidity and
temperature sensor installed in the cold
aisle.
Hot-aisle
sensor
The sensors in hot aisles can
be set to
Enable
or
Disable
.
Enable
the corresponding humidity and
temperature sensor installed in the hot
aisle.
Heat
The heat function can be set to
Enable
,
Disable
, or
Enabled
when active pwr
(for
dual-power supply scenarios).
Enable
indicates that the electric heater
will be started when the ambient
temperature is lower than the certain
temperature range of the temperature set
point.
Disable
indicates that the electric
heater will not be started.
Enabled when
active pwr
indicates that the electric
heater will be started when the main
power is active and the ambient
temperature is lower than the certain
temperature range of the temperature set
point.
Heat mode
Sets the starting mode of the
electric heater.
If
Dehumid heat
is selected, the electric
heater starts heating based on the current
temperature only after the
dehumidification function is enabled. If
Low-temp heat
is selected, the electric
heater starts heating based only on the
current temperature, no matter the
dehumidification function is enabled or
not. If
Dehumid & LT heat
is selected,
the electric heater starts heating when
the dehumidification and heating
condition or the low temperature heating
condition is met.
Humid
The humidification can be set
to
Enable
,
Disable
, or
Enabled when active pwr
(for dual-power supply
scenarios).
Enable
indicates that the electric
humidifier will be started when the
ambient humidity is lower than the
certain humidity range of the humidity
set point.
Disable
indicates that the
electric humidifier will not be started.
Enabled when active pwr
indicates that
the electric humidifier will be started
when the main power is active and the
ambient humidity is lower than the
certain humidity range of the humidity
Содержание NetCol5000-A
Страница 264: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 265: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 266: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 267: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...