4 Commissioning
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
107
SNMP Port
is set to
161
by default.
Step 6
Tap
Next Page
.
Step 7
Set SNMP trap parameters.
1.
Tap
Add
under
SNMP Trap
.
2.
Set
Trap Address
as planned and
Trap Port
to the actual port number.
Trap Port
is set to null by default.
3.
Select the
SNMP Version
. If an SNMPv3 user is configured, it is recommended that
SNMP Version
be set to
SNMPv3
.
4.
If
SNMP Version
is set to
SNMPv3
, select an
SNMPv3 user name
, and then tap
as shown in
Figure 4-22
Setting SNMP trap parameters
5.
Tap
Submit
under
SNMP Trap
.
----End
Follow-up Procedure
After a USB flash drive has been inserted into the controller USB port and successfully
identified, tap
Export File
under
MIB File
to export the MIB file to the USB flash drive for
the customer's use in accessing a third-party EMS.
Before using a USB flash drive, ensure that its data has been scanned by antivirus software
and is secure.
Содержание NetCol5000-A
Страница 264: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 265: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 266: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 267: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...