NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
4 Commissioning
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
108
Figure 4-23
Exporting the MIB file successfully
4.5.8 Setting Teamwork Control Parameters
Prerequisites
Assign teamwork group number and teamwork unit address for the teamwork controlled
precision air conditioners as follows:
Teamwork group no.: Group the precision air conditioners in adjacent areas as one, that
is, assign one teamwork group number for them. At most four teamwork groups can be
assigned (1–4).
Teamwork unit address: The address for the precision air conditioner in the same group
cannot be the same (address range: 1–32). The precision air conditioner addressed 1 is
the master one that collects, processes, and delivers data. It is recommended that you set
the unit address numbers from one to the
Total number of units
in this group.
Context
The parameters in this section are for reference only. Set actually parameter values as
required.
Procedure
Step 1
On the home screen, tap
>
Teamwork Settings
, to enter
Teamwork Settings
page, as
shown in
Содержание NetCol5000-A
Страница 264: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 265: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 266: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...
Страница 267: ...NetCol 5000 A 42 kW Air Cooled In row Precision Air Conditioner User Manual D Electrical Conceptual Diagram ...