NetCol5000-A 42 kW Air Cooled In-row Precision Air
Conditioner
User Manual
5 Operation and Maintenance
Issue 01 (2017-07-27)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
181
Step 5
Remove the liquid level detector, as shown in
Remove screws from the high liquid level detector using a Phillips screwdriver, and
remove the high liquid level detector.
Loosen the nuts on the low liquid level detector, and move the low liquid level detector
upwards to remove it.
Figure 5-29
Removing a liquid level detector
Step 6
Install the new liquid level detector and properly connect its terminals.