Item
FDC Scenario
Sensible heat
ratio
100%
System
dimensions (H x
W x D)
4150 mm x 2438 mm x 6058 mm
Installation
scenario
FDC
Power system
380–415 V AC, 3-phase, 50 Hz/60 Hz
Air filter level on
the indoor air
return side (EN
779)
G4
Air filter level on
the outdoor air
intake side (EN
779)
G3
Fan type
EC
Air volume
Indoor: 55,000 m
3
/h
Outdoor: 50,000 m
3
/h
Net weight
11,000 kg
Operating weight 11,500 kg
1
Test conditions: The outdoor dry and wet bulb temperatures are 35°C and 27°C
respectively; the indoor return and supply air temperatures are 38°C at 25% RH
and 25°C at 50% RH respectively; the external residual pressures of the indoor
and outdoor units are 150 Pa and 100 Pa respectively. If the indoor return air
temperature is lower than 38°C, the cooling capacity of the equipment is
derated.
Table 3-4 Compressor cooling specifications
Item
Specifications
Compressor type
Variable-frequency scroll compressor
Number of compressors
3
Throttling device
EEV
Refrigerant
R410A
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
3 Product Specifications
Issue 03 (2021-04-20) Copyright © Huawei Digital Power Technologies Co., Ltd.
30