monitoring point is 20°C but the return air temperature detected by the unit is
22°C, the sensor has an error of 2°C. In this case, you can set the return air
temperature calibration value to –2°C.
Procedure
Step 1 Choose Maint > Sensor Calibration on the home screen.
Step 2 Fill the calibration value based on the measured error.
----End
13.2.13 How Do I Check the Display of Normal Air Volume?
Prerequisites
Tool: differential pressure gauge (purchased onsite)
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
NO TE
Exercise caution because the unit is still energized after it is shut down on the home screen
of the display module.
Step 2 Open the side panel of the unit.
Figure 13-13 Opening the side panel
NO TE
The position of the side panel to be removed in the FDC scenario is the same as that in the
building scenario. This example shows how to open the side panel in the FDC scenario.
Step 3 Insert the negative pressure tube of the differential pressure gauge into the unit
through the hole in the return air baffle plate of the fan for about 30 mm.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
13 FAQ