SOLAR300 - SOLAR300N
EN - 117
7.4.
TEST/RECORDING OF PV-3 SYSTEM WITH REMOTE UNIT SOLAR-02
CAUTION
The maximum voltage between inputs D1, D2, A1, A2 and A3 is 1000V / CAT
IV 600V to earth. Do not measure voltages exceeding the limits indicated in
this manual. If these voltage limit values are exceeded, the user may be
exposed to electrical shocks and the instrument could get damaged
Where possible, disconnect the connecting points of the instrument, before
connecting it, by means of disconnecting switches S1 and S2
Fig. 162: Connecting the instrument to a PV-3 system with SOLAR-02
1. Check and, if necessary, change the basic settings of the instrument relative to
PV-3
configuration (see § 5.3.1, 5.3.2 and 5.3.3). Also check that the parameters of the
photovoltaic system considered correspond to the set values. For setting of
pyranometer or reference cell sensitivity please refer to the user manual of SOLAR-02
2. Use the remote unit SOLAR-02 under independent mode to perform a possible preliminary
measurement of irradiance.
CAUTION
BEFORE CONNECT DC CLAMP ON CONDUCTOR
Turn on the clamp, select the correct range and press the ZERO key to the
DC clamp in order to eliminate possible residual magnetizations in the
clamp (values of current up to 0.02A are acceptable). Connect the output
of the clamp to the IDC input of the instrument
3. Connect inputs
D1
and
D2
to the positive and negative string output pole respectively.
Connect inputs
A1
,
A2
and
A3
to the phase conductors, respecting the colors as
shown in Fig. 162
4. Connect the DC current clamp to the positive string output conductor
by respecting the
direction of the arrow
on the clamp itself as indicated in Fig. 162.
Check the status of
internal batteries of the DC clamp after the connection to the installation
5. Connect the AC clamps to the Phase L1, L2, L3 conductors
by respecting the
direction of the arrow
on the clamps as indicated in Fig. 162. Connect the output of
the clamps to the
I1
,
I2
,
I3
input of the instrument respectively
6. Supply the electric system considered in case it was temporarily put out of service for
connecting the instrument
Содержание SOLAR300
Страница 1: ...Copyright HT ITALIA 2017 Release EN 2 10 02 05 2017 SOLAR300 SOLAR300N User manual...
Страница 2: ......
Страница 159: ......