Message
Type
Description
Action
71 SYSTEM HALTED
FOR CACHE ERROR
Error
This message is displayed upon
a
no
response to message
72
CACHE ERROR <n> IGNORE?
<=NO >=YES
.
If <n> = 1.1 or 1.2: There is
currently only one cache module
in the array controller, but
the controller was previously
con
fi
gured with a second cache
module that is now missing.
If <n> = 2.1 or 2.2: A second
cache module was added to this
controller, but it contains data from
its previous array controller.
If <n> = 2.3: The single cache
module on this array controller
was replaced, but with cache
module containing data from a
different array controller. Return
the cache module to its original
array controller, power on the
system without allowing any host
I/O, and wait for cache data to be
written to hard drives. The system
can be powered off and the cache
module moved to the new location.
< = no. The array controller will
halt.
> = yes. Cache data will be
erased and operation of the array
controller will continue.
72 CACHE ERROR <n>
IGNORE? <=NO >=YES
User input
During power up, data was found
in the cache that could not be
fl
ushed to the hard drives. The
reason is either because the data
does not belong to this array
controller (the cache module was
moved from a different array
controller) or the cache data is
partial (the rest of the data is in
another cache module that was
removed from the array controller).
This error could occur if cache
modules are moved improperly.
If <n> = 1.1 or 1.2: There is
currently only one cache module
in the array controller, but
the controller was previously
con
fi
gured with a second cache
module that is now missing.
If <n> = 2.1 or 2.2: A second
cache module was added to this
controller, but it contains data from
its previous array controller.
If <n> = 2.3: The single cache
module on this array controller
was replaced, but with cache
module containing data from a
different array controller. Return
the cache module to its original
array controller, power on the
system without allowing any host
I/O, and wait for cache data to be
written to hard drives. The system
can be powered off and the cache
module moved to the new location.
< = no. The array controller will
halt.
> = yes. Cache data will be
erased and operation of the array
controller will continue.
116
MSA controller LCD panel message descriptions