ALPHABETIC REFERENCE
XI581/2 BUSWIDE OPERATOR INTERFACE
EN2B-0126 (74-3554-8)
90
Time Programme
Time Program 1
Today
Daily Programme
Weekly Programme
Annual Programme
Special Days
Select the Today Option
3.
Press Enter (
↵
) to select Today.
RESULT: The top line of the display window shows the selected time program.
If this is the first time you selected today in the current session, the
list of switch points displays.
Today : Time Program 1
C1_DO_1
▲
▲
▲
▲
C1_DO_2
*
■
Office_room_temp.
1
Canteen_room_temp.
■
Main_lights
▼
If you have already selected the TODAY program, the information
screen for the current switch point displays. See the RESULT
paragraph in the next step.
An asterisk on the same line as a user address indicates that a
TODAY program is already assigned to it.
Select a Point
4.
Use the arrow keys to move to and highlight the desired switch point and press
Enter (
↵
) to complete the selection.
RESULT: Information for the switch point displays. Example:
Today
: Heating zone east
Address
: C1_DO_1
Time from: 13:14
Time to
: 13:14
Value
: ******************
Select
Back
Create/Modify the Today Program
5.
Enter or modify information as follows:
— Use the arrow keys to move to and highlight a field and press Enter (
↵
). The
first digit you can input begins to blink.
— Press the plus and minus keys to increment and decrement the value of the
digit.
— Press the right arrow key to move to the next digit within the field.
— Repeat this input procedure until the entire field is correct. Then press Enter
(
↵
) to complete the field entry. The cursor highlights the field you just
modified.
Time from
Time the controller should
start
using the Today Program.
Input time in 24-hour (HH.MM) notation where HH=00-23 and
MM=00-59. For example, enter the time you want the
temperature in the conference room to change.
Time to
Time the controller should
stop
using the Today Program.
Input time in 24-hour (HH.MM) notation where HH=00-23 and
MM=00-59. For example, enter the time you want the
temperature in the conference room to return.
NOTES:
1. The entry in the 'Time from' field cannot be more than 24 hours after the
current system time
.