EVERYDAY OPERATIONS
XI581/2 BUSWIDE OPERATOR INTERFACE
EN2B-0126 (74-3554-8)
40
RESULT: The display window lists application programs in Flash EPROM with
their burn date and time.
Please choose Fixed Application
APPL_1
23.05.95 10:43
▲
▲
▲
▲
APPL_2
17.03.96 17:02
■
APPL_3
11.11.97 23:00 1
APPL_4_NAME_ZU_LA 26.03.98 20:30
■
APPL_5
08.08.98 14.26
▼
NOTE:
The Flash EPROM can save more than one controller application
program. If two or more application programs have the same name,
the most recently saved application program appears at the bottom of
the list of application programs.
Load application from Flash EPROM
5.
Use the arrow keys to move to and highlight the desired application program
and then press Enter (
↵
) to complete the selection.
RESULT: The application program in Flash EPROM loads in RAM and the
display window shows the Main Menu (access level 1).
CONTROLLER_07
18:16
Init
15.12.1994
Password
Alarms
Time Programmes
Trend Buffer
Data Points
System Clock
System Data
Requesting a Download
New applications can be downloaded to the controller’s Flash memory via the C-
Bus or the B-port. The controller must request the download from the device
executing the download. This option is found in the first 'Application Selection'
screen.
Application Selection
Select FLASH Application
Request Download
NOTE
:
The
Select FLASH Application
option appears only if there is at
least one application loaded in Flash EPROM.
Request Download
4.
Use the arrow keys to move to and highlight
Request Download
and press
Enter (
↵
) to complete the selection.
RESULT: The following screen appears.
Please Execute Download
NOTE
:
After an application has been downloaded, the controller checks the
CARE application’s user ID and will not start the application if the ID