EVERYDAY OPERATIONS
XI581/2 BUSWIDE OPERATOR INTERFACE
EN2B-0126 (74-3554-8)
18
Logging into a Remote Controller
Purpose
To initiate communication with a remote controller.
Performance
Only one buswide XI581/2 (local or remote) can be logged onto a controller at any
one time. However, there is no restriction as to the total number of buswide XI581/2
used on the same system bus. When XBS PCs are also on the bus, there may be
up to four XBS PCs on the same bus and one buswide XI581/2 that is in remote
access at the same time.
All XI581/2 are of equal priority, so that whichever device signs on first gains access
to a controller and no other device (local or remote) can sign on to the same con-
troller during this time.
Procedure
1.
Sign on to the XI581/2 at the desired user level (1, 2, or 3). See section "Level
2/3 Password Entry" (page 16) if you do not know how.
2.
From the Main Menu, use the arrow keys to move to and highlight
System
Data
. Then press Enter (
↵
) to complete the selection.
RESULT: The display window shows system data, including the 'Buswide
Access' option. In the following example, note that the local controller
is CONTROLLER_01.
System Data
System Info
HW-Interface Config.
Flash EPROM
Buswide Access
NOTE:
The 'Flash EPROM' item displays only if you signed on as a level-3
operator.
3.
Use the arrow keys to move to and highlight
Buswide Access
. Then press
Enter (
↵
) to complete the selection.
RESULT: The display window lists the buswide access options you can choose.
Buswide Access
CONTROLLER_01
Remote Login
Alarm Standby On
Logoff
Alarm Standby Flag
Show All DevicesAlarm Standby Off
The option 'Logoff' appears below 'Remote Login' only if you have
already logged in on the remote controller (i.e. a connection has been
established). 'Logoff' can be used to sever the connection to the
remote controller. See section "Logging Off from a Remote
Controller" (page 20) for details.
4.
Press Enter (
↵
) to select
Remote Login
(highlighted default).
RESULT: The display window lists all devices available for log-in. Controller
name and number are shown for each device.
Remote Login
CONTROLLER_07
7
▲
▲
▲
▲
CONTROLLER_09
9
■
1
■
▼