8. Series 8 I/O
Loading
8.2. Loading an IOLINK
228
Series 8 I/O User's Guide
R500
Honeywell
April 2017
8.2 Loading an IOLINK
IOLINK Load with Contents
The C300 block must be loaded before any assigned IOM blocks. Loading the C300
block automatically loads its associated configured IOLINK function blocks.
Refer to Loading IOLINK in the
C300 Controller User’s Guide
for information about
loading the C300 block and corresponding IOLINK block.
Upload error conditions
IOLINK problems preventing proper IOLINK loading are found in the Troubleshooting
and Maintenance section for:
IOLINK - loss of communications
IOLINK - re-establishing communications
8.3 Loading the IOM block the first time
Loading the IOM block present on the IOLINK
To load the IOM blocks properly ensure the following:
The IOM blocks must be loaded prior to loading any Control Modules that contain
associated channel blocks. This operation loads all loadable configuration
parameters (residing in either the C300 or the IOM device).
The load returns errors if the C300 or IOM or both are not present.
The figure below illustrates a simplified graphical representation of the encounters during
the load operation.