8. Series 8 I/O
Loading
8.3. Loading the IOM block the first time
R500
Series 8 I/O User's Guide
231
April 2017
Honeywell
Step
Action
Result
3
Ensure load check boxes are selected
for components to be loaded. Click a
component to remove/insert a check
mark.
Ensure no Control Module blocks are
selected. Click
OK
.
Initiates the sequential load to the
selected components and the load
progress dialog box appears.
TIP
If errors are detected, they are displayed in the Load progress dialog box
and a message appears if you want to continue the load or cancel,
depending on the nature of the error. Cancel the load and identify and fix
the errors. Each message includes an error code in parentheses. Note
the last number in the string. In some cases, more information about the
code number may be included in the
Control Builder Error Codes
Reference Guide
.
4
Once the load completes and the dialog
box closes, click the Monitoring tab.
IOM icon now appears in Monitoring tab.
The default state for a loaded IOM is
inactive or color code blue.
5
Refer the
document to set the IOM to its Run state.
IOM icon turns green when active.
6
Repeat this procedure to install other
IOMs.
Loading with the IOM block missing on the IOLINK
IOM blocks can be loaded without the IOM present on the link, but the following occurs:
Errors are returned on load and the IOM icon appears red in the Monitoring tab.
Refer to
Series 8 I/O block icons
to view icon appearance based on current status.