4. Series 8 IOTA Pinouts
4.3. Analog Output IOTA
Models 8X-TAOXA1, 8X-TAOXB1
R500
Series 8 I/O User's Guide
79
April 2017
Honeywell
HART/Non-HART Analog Output IOTA (Models 8X-TAOXA1, 8X-TAOXB1)
The Series 8 HART/non-HART Analog Output 6 inch, non-redundant modules supports
all 16 channels for single-ended configuration. All I/O field terminations of this IOTA is
designed to accept up to 14 gauge stranded wire.
IOTA board and connections
The Series 8 Analog Output 6 inch, non-redundant IOTA is illustrated Figure 17
The Series 8 Analog Output 12 inch, redundant IOTA is illustrated in Figure 19.
To properly wire your module to the Series 8 HART/non-HART Analog Output IOTA
with terminal block 1 (TB1) and terminal block 2 (TB2), use the following table.
Table 18 Analog Output 6 inch, HART/non-HART Analog Output, non-
redundant - terminal block 1
Terminal Block 1 (TB1)
Channel
Return
Screw
(Negative)
Analog Output
Screw
(Positive)
Channel 1
2
1
Channel 2
4
3
Channel 3
6
5
Channel 4
8
7
Channel 5
10
9
Channel 6
12
11
Channel 7
14
13
Channel 8
16
15
Channel 9
18
17
Channel 10
20
19
Channel 11
22
21
Channel 12
24
23
Channel 13
26