7. Series 8 I/O
Operations
7.6. Activating HART
R500
Series 8 I/O User's Guide
215
April 2017
Honeywell
Issuing Shutdown command
The following occurs when issuing the Shutdown command (through the
IOMCOMMAND parameter).
Field output terminals are unpowered for all channels.
INITREQ is asserted on all associated Output channel blocks.
The IOM icon in the Monitor tab becomes RED.
The detail display shows Alive state.
7.6 Activating HART
The Series 8 I/O's fundamental Analog Input and Analog Output channel blocks support
HART communications protocol. To enable HART, you must assign the channel to a
HART IOM, and set HENABLE to TRUE.
to review Series 8 configuration form tabs and parameter
availability for HART.
Assigning a channel to HART - Series 8
Prerequisites
Control Builder is running
A control module was created