9. Series 8 I/O
Link Fiber Optic Extenders (FOE)
9.3. Component mounting sequence
246
Series 8 I/O User's Guide
R500
Honeywell
April 2017
Mounting the FOE module onto the IOTA
Prerequisites
It is required to attach the FOE module to the IOTA prior to its mounting to the carrier.
All wiring and pre-fabricated cables are available and labeled as applicable should also
be established.
To mount the module onto the back panel
Step
Action
1
Align the FOE screws (located on the flange) with the holes on the back
panel
2
Tighten the four screws that attach the base of the FOE module to the
back panel (using a Phillips screw-driver).
Mounting the FOE module/back panel assembly to the carrier
Prerequisite
Before installing the FOE module/back panel assembly in the cabinet, ensure that all
wiring and pre-fabricated cables are available.
ATTENTION
Prior to installing or servicing the FOE assembly (FOE module on the
back panel) to the carrier, the power connector needs to be removed.
After mounting the FOE assembly to the carrier and installing IOlink
connector, power connector can be re-installed.
To mount the FOE module/back panel assembly to the carrier
Step
Action
1
Select the desired mounting location on the carrier and align the mounting
holes in the back panel with the screw-hole locations on the carrier.
6-inch back panel board 4 mounting screws
2
Using a #2 Phillips screwdriver, secure the FOE assembly to the carrier.
Connecting the IOLINK interface cable to the FOE module
ATTENTION
The lOLINK interface cable should be connected to the FOE module before it
is powered up.