5. Series 8 I/O
Configuration Form Reference
5.1. Overview
106
Series 8 I/O User's Guide
R500
Honeywell
April 2017
A.
If the IOTA is redundant, perform the following steps depending on the IOM type.
For Analog and Digital Input Modules, perform the following steps.
Step
Action
1
From Control Builder Monitoring View, for each loaded Input Channel, set
PV
Source
option
(PVSRCOPT)
to
ALL
.
2
From Control Builder Monitoring View, for each loaded Input Channel, set
PV
Source
(PVSOURCE)
to
MAN
.
3
From Control Builder Monitoring View, select the IOM and perform an
Upload
operation.
4
From Control Builder Monitoring View, select the IOM and perform an
Update
to Project
.
5
From Control Builder Project View, select the IOM and enable Redundancy
using the checkbox for
This IOM is redundant
(REDOPT) parameter.
6
From Control Builder Project View, select the IOM and perform a
Load
.
7
Ensure the IOM state is in Run.
8
If the channels were not selected to activate during the load operation, then
Activate
them.
9
From Control Builder Monitoring View, for each loaded Input Channel, set
PV
Source
option
(PVSRCOPT)
to
ONLYAUTO
.
ATTENTION
PV Source (PVSOURCE)
automatically goes to
AUTO
.
10
From Control Builder Monitoring View, select IOM and perform an
Upload
operation to ensure ERDB Monitor database matches current configuration in
IO module.
11
From Control Builder Monitoring View, select IOM and perform an
Update to
Project
operation to ensure ERDB Project database matches Monitor
database.
For Analog and Digital Output Modules, perform the following steps.
Step
Action
1
From Control Builder Monitoring View, select the IOM and perform an
Upload
operation to ensure ERDB Monitor database matches current configuration in