5. Series 8 I/O
Configuration Form Reference
5.11. Configuring Server History tab - IOM block
124
Series 8 I/O User's Guide
R500
Honeywell
April 2017
Step
Action
2
Proceed to the following procedures to configure parameters on the
remaining tabs for I/O Module, or click
OK
to accept only the changes made
so far and return to the Project tree.
Table 30 Server History tab parameters
Plain text
Parameter name
User
configurable
Notes
Control Level
SCANCTRLLVL
Yes
Indicates Server control level to be
associated with this function.
Number of
History
Parameters
HIST.NUMPARAM
S
Yes
Defines number of history
parameters to be included in
History Configuration table.
Parameter
HIST.PARAM
Yes
Valid parameter name for a
parameter associated with the
given point that is to be collected
and stored as historical data at
predetermined intervals.
Description
No
Provides a brief description of the
entered parameter.
FAST
HIST.FAST
Yes
Select the Fast type of history
collection.
STD
HIST.STD
Yes
Select the Standard type of history
collection.
EXTD
HIST.EXTD
Yes
Select the Extended type of
history collection.
EXC
HIST.EXC
Yes
(
Station
only)
Select the Exception type of
history collection.
Gating Parameter
Yes
Optional gating parameter to
define conditions under which data
for this parameter should be
collected.
Gate State
Yes
Defines gate state for configured
gating parameter.