HV350 Mini Frequency Inverter User Manual
96
reducing its output frequency. When the detected bus voltage is lower than the point,
the Dec running will be restored, as shown in Fig.6-32.
time
time
DC Bus voltage
Stall over voltage point
Output frequency
Fig. 6-32 Over voltage stall function
Pd.03
Stall over voltage point
Setting range
:
120.0%~150.0%
Stall over ovtage point = 120.0%~150.0% inverter‘s rated peak voltage
Pd.04
Selection of overload pre-alarm detection
Setting range
:
0
,
1
0:
Overload is only monitored during constant speed operation, and alarms
when overload occurs;
1:
Overload is monitored all the time, and alarms when overload occurs;
Pd.05
Overload detection threshold
Setting range
:
20-180%
Pd.06
Overload pre-alarm delay
Setting range
:
0-60.0s
PD.05 defines the threshold value for overload alarm. It is a percentage of rated
current.
Pd.07
Auto current limiting threshold
Setting range
:
20.0
~
150.0%
(
drive‘s
rated output current
)