HV350 Mini Frequency Inverter User Manual
113
4.2 Function code
Function code
Description
03H
Read data
06H
Modify data
08H
Loop detection
2
.
Function code description
RTU
(
1
)
Read data
Frame head and frame tail are used to ensure input time (without any
information) larger than 10ms. Each time, reading data should be less than 30 bytes.
Message format of master request:
Slave
address
Function
code
Start address of
data
Data quantity
(Unit: word)
Redundancy
check
1 byte
03H
MSB LSB
MSB
LSB
LSB
MSB
Message format of slave response:
Slave
address
Function
code
Data
quantity
Data 1
…
Data n
Redundancy
check
1 byte
03H
1 byte
MSB LSB
… MSB LSB LSB MSB
MSB: high byte of double byte number;
LSB: low byte of double byte number.
(
2
)
Modify data
Message format of master request:
Slave
address
Function
code
Start address of
data
Modified
value
Redundancy
check
1 byte
06H
MSB
LSB
MSB
LSB
LSB
MSB
Message format of slave response: