HV350 Mini Frequency Inverter User Manual
28
4.6.2
Switch of the running parameters
In running state, maximum 15 running state parameters can be displayed by HV350
drive via
SHIFT
key.
4.7 Motor auto-tuning procedure
Before selecting vector control mode, user should input motor parameters correctly.
HV350 drive can get motor‘s standard parameters according to the parameters on
nameplate; In order to get better control performance, you can control the drive to
perform auto-tuning on the motor, so as to get accurate motor parameters.
Parameter tuning can be done through P3.05.
1.
S
et F0.01 parameter to 0 to select panel running command control mode;
2.
According the motor
’s name-plat,Set P3.00
、
P3.01
、
P3.02
、
P3.03
、
P3.04 parameter in proper order
。
3.
Set P3.05 to1
,
Slect static auto- tuning
,
Or set P3.05 to 2
,
Slect overall auto- tuning
,
Press
“
SET
”
key
。
4.
Press RUN key to start motor auto-tuning, After tuning, the motor stops.