HV350 Mini Frequency Inverter User Manual
118
‗2‘
‗2‘
‗A‘
‗A‘
‗B‘
‗B‘
LRC
‗3‘
LRC
‗3‘
‗A‘
‗A‘
END
CR
END
CR
LF
LF
RTU mode:
Format of query message: Format of response message:
Slave address
01H
Slave address
01H
Function code
08H
Function code
08H
Sub-function code 00H
Sub-function code 00H
00H
00H
Data content
12H
Data content
12H
ABH
ABH
Low byte CRC
ADH
Low byte CRC
ADH
High byte CRC
14H
High byte CRC
14H
4.4 Control word and status word
1. Information of status word (2 bytes)(1000H)
Bit0
=1, FWD
=0, REV
Bit1
=1, Drive failure
=0, No drive failure
Bit2
=1, Running state
=0, Stopping state
Bit3
=1, Modifying parameter valid
=0, Modifying parameter invalid
Bit4
=1, Frequency setting via RS485