HV350 Mini Frequency Inverter User Manual
93
Pb.01
Preset traverse frequency
Setting range
:
0.00~400.0Hz
Pb.02
Hold time of preset traverse frequency
Setting range
:
0.0~3600s
Pb.01 defines drive‘s operating frequency before entering traverse operation.
In auto mode, Pb.02 defines the hold time of preset traverse frequency before
traverse operation. In manual mode, Pb.02 setting is invalid. Refer to Fig. 6-31 for
details.
Pb.03
Preset central frequency
Setting range
:
0.00~400.0 Hz
Traverse operation is shown in Fig. 6-31.
Pb.04
Travers amplitude
Setting range
:
0.0~50%
Travers amplitude = Preset central frequency×Fb.04
Pb.05
Step frequency
Setting range
:
0.0~50%
Refer to Fig. 6-31. If it is set at 0, then there will be no step frequency.
Pb.06
Traverse cycle
Setting range
:
0.1~999.9S
It defines the period of traverse operation including rising and falling time.
Pb.07
Rise time of triangular wave
Setting range
:
0.0~100.0%
It defines the rising time (Pb.06×Pb.07 s) of traverse operation, and falling
time (Fb.06×(1-Fb.07) s). Please refer to Fig. 6-31.
t
Step frequency
=AW*Pb.05
Traverse amplitude
AW= Fset*Pb.04
Hold time of
preset traverse
frequency
Pb.02
Accerlate
according to
Acc time
Run command
Stop command
Decelerate
according to
Dec time
Traverse cycle
Pb.06
Rise time of
triangular wave
=Pb.07*Pb.06
Operating frequency Hz
Upper limit of traverse frequency
FH
central frequency
Pb.03
FL
Preset traverse frequency
Pb.01
Lower limit of traverse frequency