HV350 Mini Frequency Inverter User Manual
76
17
26: Counter trig signal
It is the input terminal of the drive‘s internal counter. If the input signal of the
terminal changes from ON to OFF, the counting value is increased by 1.
18.
27: Counter reset signal
This terminal is used to clear the inverter's internal counter, and is used in
conjunction with Function 24 "Counter trig signal".
When the terminal is ON, internal counter is cleared to 0.
19.
28: PID dormancy waking up
i.
When PA.17=2 and this terminal is ON, PID control will exit
dormancy state and execute normal PID function.
20
.
29:
switch between PID positive mode and negative mode:
When PA.00 is set to 0
,PID positive mode is selected with the terminal is off ;
negative mode is selected with the terminal is on.
21. 30:―
Emergence stop”
If the terminal defined with the function is on, the inverter is in
emergence stop
status( motor free stop)
P6.09
Programmable relay 1
Setting range
:
0
~
20
P6.10
Output terminal Y1 definition
Setting range
:
0
~
20
Function selection of programmable relay output terminals and open
collector output terminals is shown in the table below.
Content
Function
Content
Function
0
Programmable relay 1: No
operation
Output
terminal
Y1:
No
operation
11
Over voltage stall
1
Drive ready
12
External stopping command
2
Drive running signal1
13
Preset counting value
arriving
3
Drive running signal2
14
Specified counting value
arriving