HV350 Mini Frequency Inverter User Manual
100
PH.04
IPM heatsink temperature
1
Setting range
:
0
~
100
℃
PH.05
IPM heatsink temperature
2
Setting range
:
0
~
100
℃
Display IPM heatsink temperature.
PH.06
1st fault type
Setting range
:
PH.07
2nd fault type
Setting range
:
PH.08
3rd fault type
Setting range
:
PH.06~PH.08 are used for memorizing the latest three fault types, and can
record the voltage, current, frequency and terminal state at the last fault (in
PH.09~PH.13) for checking.
Please refer to Chapter 7 for fault descriptions.
PH.09
Bus voltage at last fault
(
V
)
Setting range
:
0
~
999
PH.10
Output current at last fault
(A)
Setting range
:
0
~
999.9
PH.11
Frequency setting at last fault
(
Hz
)
Setting range
:
0
~
400.0
PH.12
Running frequency at last fault
(
Hz
)
Setting range
:
0
~
400.0
PH.13
I/O state at last fault
Setting range
:
0
~
511
PH.14
Total operating time
Setting range
:
0
~
9999
PH.15
Software version
Setting range
:
0
~
9.99
PH.16 Keyboard
Software version
Setting range
:
0
~
9.99
PH.12At last time, I/O Status correspond as blow:
relay1
Y1
X7
X6
X5
X4
X3
X2
X1
Bit8
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Chapter 7 Fault diagnosis and troubleshooting
7.1 Fault query at fault
If control power supply is normal at fault, the drive will be in fault displaying status
all the times. At this time, user can enter parameter group PH to get related information