4-36
Chapter 4
For parameter configuration
[Input terminal function list]
Functio
n code
Symb
ol
Function
name
Description
000
no
Not use
-
001
FW
Forward rotation Activating (ON) only one of them
will grant forward or reverse
rotation command.
⇒
[AA111]
002
RV
Reverse rotation
003
CF1
Multi speed
selection 1
Changing the states of these
terminals, allows to set different
motor speeds and change among
them.
⇒
[Ab110]
~
[Ab-25],
[Ab210]
004
CF2
Multi speed
selection 2
005
CF3
Multi speed
selection 3
006
CF4
Multi speed
selection 4
007
SF1
Multi speed Bit-7
008
SF2
Multi speed Bit-2
009
SF3
Multi speed Bit-3
010
SF4
Multi speed Bit-4
011
SF5
Multi speed Bit-5
012
SF6
Multi speed Bit-6
013
SF7
Multi speed Bit-6
014
ADD
Trigger for
frequency
addition[Ab105]
When is turned ON, adds the
specified frequency value.
⇒
[AA106]
015
SCH
G
Speed reference
change
Main speed(OFF)/Sub-speed (ON),
to change between them use
⇒
[AA105].
016
STA
3-wire Start
If [STA] is ON, start the motor. If
[STP] is ON stop the motor.
Forward operation direction if [FR]
is (OFF), reverse operation direction
if is (ON).
⇒
[AA111]
017
STP
3-wire Stop
018
FR
Forward Over
Travel
019
AHD
analog command
holding
When the Analog inputs Ai1,2,3 are
in use, if AHD terminal is in ON
state, holds the Analog terminal
value.
⇒
[AA101]
020
FUP
Remote control
Speed-UP
function
If the frequency can be set ([AHD]
ON included), [FUP] ON accelerates,
and [FDN] ON decelerates. [UDC]
returns to the saved value.
⇒
[CA-62]
~
[CA-66]
021
FDN
Remote control
Speed-DOWN
function
022
UDC
Remote control
data clearing
023
F-OP
Force operation
If ON, switch set parameters.
⇒
[CA-68],[CA-69]
024
SET
2nd-motor
control
Change between 1st-motor (OFF)
and 2nd-motor (ON).
⇒
By parameter
028
RS
Reset
Reset trip
⇒
[CA-61],[bb-41]
029
JG
Jogging
Activates Jogging operation.
⇒
[AG-20],[AG-21]
030
DB
External Dynamic
brake
Enables the DC braking operation
⇒
[AF101]
~
[AF109]
031
2CH
2-step
Acceleration/Dec
eleration
If ON, changes the Acc/Decel time.
⇒
[AC115]
032
FRS
Free run stop
If ON allows the motor to free run.
⇒
[AA115],[bb-40]
033
EXT
External fault
If ON error E012 occurs.
⇒
Trip E012
034
USP
unattended
start protection
ON if at the start-up, the RUN
command was issued right at the
start up, E013 error.
⇒
Tripping E013
035
CS
Commercial
Supply change
When changing to the public
electric grid, if it is ON, will cut the
output.
036
SFT
Soft-Lock
If ON, disables parameter changes.
⇒
[UA-21]
037
BOK
Answer back
from Brake
Here is inputted the brake
confirmation signal for the brake
control.
[Input terminal function list]
Function
code
Symbol Function name Description
038
OLR
Accumulation
input power
clearance
Switches between Overload limit
1(OFF) and 2(ON).
⇒
[bA122]
~
[bA128]
039
KHC
Accumulation
output power
clearance
If ON, clears the Accumulated input
power monitor.
⇒
[UA-14]
040
OKHC
Disable PID1
If ON, clears the Accumulated
output power monitor.
⇒
[UA-12]
041
PID
PID1
integration
reset
If ON, disables PID1 and changes
the PID target value for the
frequency reference.
⇒
[AH-01]
042
PIDC
Disable PID2
If ON, clears the integral value of
the control.
⇒
[AH-62],[AH-65]
043
PID2
PID2
integration
reset
If ON, disables PID2 and changes
the PID target value for the
frequency reference.
⇒
[AJ-01]
044
PIDC2
Disable PID3
If ON, clears the integral value of
the control.
⇒
[AJ-14]
046
PID3
PID3
integration
reset
If ON, disables PID3 and changes
the PID target value for the
frequency reference.
⇒
[AJ-21]
046
PIDC3
Disable PID4
If ON, clears the integral value of
the control.
⇒
[AJ-34]
047
PID4
PID4
integration
reset
If ON, disables PID4 and changes
the PID target value for the
frequency reference.
⇒
[AJ-41]
048
PIDC4
Multi set-point
selection 1
If ON, clears the integral value of
the control.
⇒
[AJ-54]
051
SVC1
Multi set-point
selection 2
The target value can be selected by
changing the pattern of ON/OFF
states.
⇒
[AH-06]
052
SVC2
Multi set-point
selection 3
053
SVC3
Multi set-point
selection 4
054
SVC4
PID gain change
055
PRO
PID output
switching 1
Switches between Gain 1(OFF) and
Gain 2(ON).
056
PIO
PID output
switching 2
Switches PID Output 1 to 4 by
(PIO1:PIO2).
PID1 Enable(OFF:OFF)
PID2 Enable(OFF:ON)
PID3 Enable(ON:OFF)
PID4 Enable(ON:ON)
057
PIO2
SLEEP condition
ativation
058
SLEP
WAKE condition
ativation
In case it is used in Sleep terminal
functions, when ON, it activates.
⇒
[AH-85]
059
WAKE
Torque limit
enable
In case it is used in Wake terminal
functions, when ON, it activates.
⇒
[AH-93]
060
TL
Torque limit
selection bit 1
If ON, enables torque limit.
061
TRQ1
Torque limit
selection bit 2
The target value can be selected by
changing the pattern of ON/OFF
states.
062
TRQ2
Accumulation
input power
clearance
Содержание P1-00041HFEF
Страница 6: ...0 5 Contents Contents Memo ...
Страница 42: ...2 26 Chapter 2 Installation and Wiring Memo ...
Страница 129: ...Index Index 3 memo ...
Страница 130: ...Index Index 4 memo ...