2-11
Chapter 2
Installation and Wiring
400V class
•
For ND rating
•
For LD/VLD rating
Device model name on above table shows example selection. The
device selection should be made in base on rated current, short
circuit current capability and accordance to the local electrical
legislation.
Applicable motor capacity is based on Hitachi 400Vac, 60Hz, 4 pole
IE3 motor.
Refer to the wire gauge table on chapter 2-8.
Electrical endurance for AC-1 magnetic contactor is 500000 times,
however, for emergency stop in motor operation will be only 25
times.
Select AC-3 class magnetic contactor for inverter output for
application which has an emergency stop or commercial power line
operation.
When selecting oversize inverter capacity compare to motor rating,
select according to the inverter capacity
Model
P1-*******
(P1-****)
Applicable
Motor
(kW)
Applicable devices (Input Voltage 400
~
440V)
Without reactor
(DCL or ACL)
With reactor
(DCL or ACL)
Earth-leakage breaker
(ELB)
Magnetic Contactor
(MC)
Earth-leakage breaker
(ELB)
Magnetic Contactor
(MC)
Example
model
Current
Rate
AC-1
AC-3
Example
model
Current
Rate
AC-1
AC-3
P1-00041-H(P1-007H)
0.75
EX50C
5
HS8
HS8
EX50C
5
HS8
HS8
P1-00054-H(P1-015H)
1.5
EX50C
10
HS8
HS8
EX50C
5
HS8
HS8
P1-00083-H(P1-022H)
2.2
EX50C
10
HS8
HS8
EX50C
10
HS8
HS8
P1-00126-H(P1-037H)
3.7
EXK50-C
15
HS8
HS10
EX50C
10
HS8
HS10
P1-00175-H(P1-055H)
5.5
EXK50-C
20
HS8
HS20
EXK50-C
15
HS8
HS20
P1-00250-H(P1-075H)
7.5
EXK50-C
30
HS8
HS25
EXK50-C
20
HS20
HS25
P1-00310-H(P1-110H)
11
EXK50-C
40
HS20
HS35
EXK50-C
30
HS25
HS35
P1-00400-H(P1-150H)
15
EXK50-C
50
HS25
HS50
EXK50-C
40
HS35
HS50
P1-00470-H(P1-185H)
18.5
EXK100-C
75
HS35
HS50
EXK50-C
50
HS50
HS50
P1-00620-H(P1-220H)
22
EXK100-C
75
HS50
H65C
EXK60-C
60
HS50
H65C
P1-00770-H(P1-300H)
30
EXK100-C
100
HS50
H80C
EXK100-C
75
H80C
H80C
P1-00930-H(P1-370H)
37
RXK125-S
125
H80C
H100C
EXK100-C
100
H80C
H100C
P1-01160-H(P1-450H)
45
EXK225
150
H80C
H125C
RXK125-S
125
H100C
H125C
P1-01470-H(P1-550H)
55
EXK225
200
H100C
H125C
EXK225
150
H150C
H125C
P1-01760-H(P1-750H)
75
RXK250-S
250
H150C
H200C
EXK225
200
H200C
H200C
P1-02130-H(P1-900H)
90
EX400
300
H200C
H250C
EXK225
225
H200C
H250C
P1-02520-H(P1-1100H)
110
EX400
400
H200C
H300C
EX400
300
H250C
H300C
P1-03160-H(P1-1320H)
132
EX600B
500
H250C
H300C
EX400
350
H400C
H400C
Model
P1-*******
(P1-****)
Applicable
Motor
(kW)
Applicable devices (Input Voltage 400
~
440V)
Without reactor
(DCL or ACL)
With reactor
(DCL or ACL)
Earth-leakage breaker
(ELB)
Magnetic Contactor
(MC)
Earth-leakage breaker
(ELB)
Magnetic Contactor
(MC)
Example
model
Current
Rate
AC-1
AC-3
Example
model
Current
Rate
AC-1
AC-3
P1-00041-H(P1-007H)
1.5
EX50C
10
HS8
HS8
EX50C
5
HS8
HS8
P1-00054-H(P1-015H)
2.2
EX50C
10
HS8
HS8
EX50C
10
HS8
HS8
P1-00083-H(P1-022H)
3.7
EXK50-C
15
HS8
HS10
EX50C
10
HS8
HS8
P1-00126-H(P1-037H)
5.5
EXK50-C
20
HS8
HS20
EXK50-C
15
HS8
HS20
P1-00175-H(P1-055H)
7.5
EXK50-C
30
HS8
HS25
EXK50-C
20
HS8
HS20
P1-00250-H(P1-075H)
11
EXK50-C
40
HS20
HS35
EXK50-C
30
HS8
HS25
P1-00310-H(P1-110H)
15
EXK50-C
50
HS25
HS50
EXK50-C
40
HS20
HS35
P1-00400-H(P1-150H)
18.5
EXK100-C
75
HS35
HS50
EXK50-C
50
HS20
HS35
P1-00470-H(P1-185H)
22
EXK100-C
75
HS50
H65C
EXK60-C
60
HS35
HS50
P1-00620-H(P1-220H)
30
EXK100-C
100
HS50
H80C
EXK100-C
75
HS50
H65C
P1-00770-H(P1-300H)
37
RXK125-S
125
H80C
H100C
EXK100-C
100
HS50
H65C
P1-00930-H(P1-370H)
45
EXK225
150
H80C
H125C
RXK125-S
125
H65C
H80C
P1-01160-H(P1-450H)
55
EXK225
200
H100C
H125C
EXK225
150
H80C
H100C
P1-01470-H(P1-550H)
75
EX400
250
H150C
H200C
EXK225
200
H100C
H125C
P1-01760-H(P1-750H)
90
EX400
300
H200C
H250C
EXK225
225
H125C
H150C
P1-02130-H(P1-900H)
110
EX400
400
H200C
H300C
EX400
300
H150C
H250C
P1-02520-H(P1-1100H)
132
EX600B
500
H250C
H300C
EX400
350
H200C
H250C
P1-03160-H(P1-1320H)
160
EX600B
600
H400C
H400C
EX400
400
H250C
H300C