4-40
Chapter 4
For parameter configuration
[CC-20]
~
[CC-33]
Output terminal response
Code/Name
Range (unit)
Initial
value
CC-20
Output terminal [11] on-delay time 0.00
~
100.00(s)
0.00
CC-21
Output terminal [11] off-delay time 0.00
~
100.00(s)
0.00
CC-22
Output terminal [12] on-delay time 0.00
~
100.00(s)
0.00
CC-23
Output terminal [12] off-delay time 0.00
~
100.00(s)
0.00
CC-24
Output terminal [13] on-delay time 0.00
~
100.00(s)
0.00
CC-25
Output terminal [13] off-delay time 0.00
~
100.00(s)
0.00
CC-26
Output terminal [14] on-delay time 0.00
~
100.00(s)
0.00
CC-27
Output terminal [14] off-delay time 0.00
~
100.00(s)
0.00
CC-28
Output terminal [15] on-delay time 0.00
~
100.00(s)
0.00
CC-29
Output terminal [15] off-delay time 0.00
~
100.00(s)
0.00
CC-30
Output terminal [16] on-delay time 0.00
~
100.00(s)
0.00
CC-31
Output terminal [16] off-delay time 0.00
~
100.00(s)
0.00
CC-32
Output terminal [AL] on-delay time 0.00
~
100.00(s)
0.00
CC-33
Output terminal [AL] off-delay time 0.00
~
100.00(s)
0.00
・
Sets the delay time since the output terminal changes,
until it actually become responsive.
[Intelligent output terminal function list]
Function
code
Symbol
Function name
Description
000
no
Not use
001
RUN
Running
While output is active
002
FA1
Constant-speed
reached
When constant speed
reached, ON
003
FA2
Set speed
overreached
ON at reaching the specified
frequency or more
004
FA3
Set frequency
reached
ON only at reaching the
specified frequency
005
FA4
Set speed
overreached 2
ON at reaching the specified
frequency 2 or more
006
FA5
Set speed reached
ON only at reaching the
specified frequency 2
007
IRDY
inverter ready
ON when inverter is ready
008
FWR
Forward rotation
ON while in forward drive
009
RVR
Reverse rotation
ON while in reverse drive
010
FREF
Speed referenc =
Keypad is selected
ON if the frequency
reference is from keypad
011
REF
Run command =
Keypad is selected
ON
if
the
motion
operation
is
from
operation keypad
012
SETM
2nd control is
selcted
ON if 2nd-motor selected
016
OPO
Option output
Controlled by the Option
017
AL
Alarm
ON when trip happens
018
MJA
Major failure
ON if major failure trips
019
OTQ
Over-torque
ON if torque is exceeded
020
IP
Instantaneous
power failure
ON if control power drops
021
UV
Undervoltage
ON if main voltage drops
022
TRQ
Torque limited
ON if torque limit operates
023
IPS
IP-Non stop function
is active
ON if set in power loss
024
RNT
Accumulated
operation time over
ON if set time is exceeded
025
ONT
Accumulated
power-on time over
ON if set time is exceeded
026
THM
Electronic thermal
alarm signal(MTR)
ON if motor thermal
integral value exceeds set
value
027
THC
Electronic thermal
alarm signal(CTL)
ON if inverter thermal
integral value exceeds set
value
029
WAC
Capacitor life
warning
ON by life warning
030
WAF
Cooling-fan speed
drop
ON by life warning
031
FR
Starting contact
signal
On while in operation
032
OHF
Heat sink overheat
warning
ON when the heatsink is
overheated.
033
LOC
Low-current
indication signal
ON if output current is less
that the specified value
034
LOC2
Low-current
indication signal 2
ON if output current is less
that the specified value
035
OL
Overload notice
advance signal (1)
ON if output current
exceeds specified value
036
OL2
Overload notice
advance signal (2)
ON if output current
exceeds specified value
037
BRK
Brake release
ON when brake releases
038
BER
Brake error
ON if abnormality in
sequence happens
039
CON
Contactor control
ON if contactor releases
Содержание P1-00041HFEF
Страница 6: ...0 5 Contents Contents Memo ...
Страница 42: ...2 26 Chapter 2 Installation and Wiring Memo ...
Страница 129: ...Index Index 3 memo ...
Страница 130: ...Index Index 4 memo ...