4-29
Chapter 4
For parameter configuration
[bA120]
~
[bA128]
Overcurrent suppression function setting
Code/Name
Range (unit)
Initial
value
bA120
Overcurrent
suppression enable, 1st-motor
00(Disable)/
01(Enable)
00
bA121
Overcurrent
suppression level, 1st-motor
Inverter ND rated
current×(0.20
~
2.00)
*1)
*1) Inverter ND rated current×1.80
・
Overcurrent can be suppressed, but in that case torque
drop can occur. Disable it in cases such as cranes.
Overload restriction function settings
Code/Name
Range (unit)
Initial
value
bA122
Overload restriction 1
enable, 1st-motor
00(Disable)/
01(Enable during Acc. and
constant speed)/
02(Constant speed only)/
03(Enable during Acc. and
constant speed-Acc. during
regeneration)
01
bA123
Overload restriction 1
level, 1st-motor
Inverter rated current
×(0.20
~
2.00)
*2)
bA124
Overload
restriction 1 deceleration
time, 1st-motor
0.10
~
3600.00(s)
1.00
bA126
Overload restriction 2
enable, 1st-motor
00(Disable)/
01(Enable during Acc. and
constant speed)/
02(Constant speed only)/
03(Enable during Acc. and
constant speed - Increase
frequency during
regeneration)
00
bA127
Overload restriction 2
level, 1st-motor
Inverter rated current
×(0.20
~
2.00)
*2)
bA128
Overload
restriction 2 deceleration
time, 1st-motor
0.10
~
3600.00(s)
1.00
*2) Inverter rated current×1.50
・
When the current is increased, the overload restriction
function reduces the current automatically by lowering
the frequency.
・
Using [OLR] function state, the overload restriction 1
(OFF) and overload restriction 2 (ON) can be used.
[bA-30]
~
[bA145]
Deceleration / stop at power loss (Non-stop)
Code/Name
Range (unit)
Initial value
bA-30
Selection of
deceleration/stop in the
event of a power loss
00(Disable)/
01(Decel. stop)/
02(Decel. stop: with
resume)/
03(Decel. stop:
return to origin)
00
bA-31
DC voltage trigger
level during power loss
(200V class)
0.0
~
400.0(Vdc)
(400V class)
0.0
~
800.0(Vdc)
(200V class)
220.0
(400V class)
440.0
bA-32
Overvoltage
threshold during power loss
(200V class)
0.0
~
400.0(Vdc)
(400V class)
0.0
~
800.0(Vdc)
(200V class)
360.0
(400V class)
720.0
bA-34
Deceleration time
during power loss
0.01
~
3600.00(s)
1.00
bA-36
Initial output
frequency decrease during
power loss
0.00
~
10.00(Hz))
0.00
bA-37
Proportional gain
for operation at power loss
0.00
~
2.55
0.20
bA-38
Integral time for
operation at power loss
0.000
~
65.535(s)
0.100
・
If the DC voltage of the main circuit is lower than the
level of [bA-31], the inverter decelerates to create a
regenerative state.
・
When [bA-30]=01, if the DC voltage drops, deceleration
starts from the value of the actual frequency command
to the [bA-36], according to the deceleration time
[bA-34]. Once the DC voltage exceeds the [bA-32], the
deceleration is temporally stopped.
・
When [bA-30]=02/03, if the DC voltage drops below DC
target level setting [bA-32], the output frequency is
decreased by PI control to put in regenerative mode
and the DC voltage is maintained at [bA-32] target
level.
Overvoltage suppression - deceleration
Code/Name
Range (unit)
Initial value
bA140
Overvoltage suppression
enable, 1st-motor
00(Disable)/
01(DC, constant decel.)
02(Enable acceleration)/
03(Enable Acc. at
constant speed & decel.)
00
bA141
Overvoltage suppression
level, 1st-motor
(200V class)
330.0
~
390.0(Vdc)
(400V class)
660.0
~
780.0(Vdc)
(200V class)
380
(400V class)
760
bA142
Overvoltage
suppression action time,
1st-motor
0.00
~
3600.00(s)
1.00
bA144
Overvoltage
suppression proportional
gain, 1st-motor
0.00
~
2.55
0.50
bA145
Overvoltage suppression
integral time, 1st-motor
0.000
~
65.535(s)
0.060
・
When [bA140]=01, the deceleration time is increased
until stop so the DC voltage do not cross over the
[bA141] level.
・
When [bA140]=02/03, accelerates temporally so the DC
voltage do not cross over [bA141] level.
Inverter output
frequency
Overload restriction level
[bA123]/[bA127]
Output current
Reference
frequency
Deceleration according to
the deceleration time at
overload restriction
[bA124]/[bA128]
Maximum frequency
[Hb105]
[Hd105]