Chapter 5 Control of EH-SIO
5 - 6
t parameter
The t parameter is used 5 bits in all. The configuration of t parameter is shown below.
t
[0]
[1]
t+1
t+2
[2]
[3]
t+3
[4]
t+4
[0] TRNS 9 execution flag (Bit set by user)
[3] TRNS 9 initialization request flag (Bit set by user)
[1] TRNS 9 normal completion flag
[2] TRNS 9 error flag
[4] TRNS 9 initialization completion flag
Figure 5.8 Configuration of t parameter (TRNS 9 command)
[0] TRNS 9 execution flag
When this bit is set to ON, TRNS 9 command is executed. (The command and data are sent to EH-SIO.) After
TRNS 9 command is completed, it is set to OFF automatically.
[1] TRNS 9 normal completion flag
If TRNS 9 command is completed properly, this bit is set to ON. When the command execution flag (t+0) is set
to ON, it is set to OFF automatically.
[2] TRNS 9 error flag
If TRNS 9 command is not completed properly, this error flag will be set to ON. When a command execution
flag (t+0) is set to ON, it is set to OFF automatically.
[3] TRNS 9 initialization request
When this bit is set to ON, the status of the TRNS 9 command and a handshake with EH-SIO are returned to an
initial state. Moreover, EH-SIO is returned to the state after initial setting completion. (All the packets that
EH-SIO had received till then are also cleared.)
Please turn on, when a command timeout error occurs. If an initialization is completed, it is set to OFF
automatically. (It is not necessary to turn off this flag by user program.)
[4] TRNS 9 initialization completion
If the initialization of TRNS 9 command is completed, it is set to ON automatically. If a command execution flag
(t+0) or a TRNS 9 initialization request (t+3) is set to ON, it is set to OFF automatically.
« Note »
TRNS 9 command performs initialization of the internal work memory and so on at the first scan.
Therefore, please do not turn on a TRNS 9 command execution flag with RUN after 1 scan.
If two or more TRNS 9 commands are executed to the same communication port, TRNS 9 command
will not perform properly. Please make a program so several execution flags not to be ON in parallel.
Please do not set the area of s parameter and t parameter as power failure memory. Since former
information remains next time at the time of power supply ON, TRNS9 may stop operating normally.
Please do not turn off an initialization request flag (t+3) by user program. (Since it turns off
automatically by the system when initializing is completed.)
Содержание EH-150 Series
Страница 1: ...HITACHI PROGRAMMABLE CONTROLLER Serial Communication Module EH SIO APPLICATION MANUAL NJI 443F X ...
Страница 2: ......
Страница 10: ...M E M O ...
Страница 30: ...Chapter 4 Installation 4 10 M E M O ...
Страница 156: ...Chapter 7 System setup 7 12 M E M O ...
Страница 164: ...Chapter 8 Daily and Periodic Inspection 8 8 M E M O ...