Chapter 6 Communication mode
6 - 95
S
imp
le
d
at
a l
ink
[7] Station number, words of slave station
One word for one station. Specify as many words as slave station number.
(1) Station number
Specify station number in high byte in BCD.
The valid range is from H01 to H31. If the value is 0 or more than H32 or including A to F characters, the initial
setting error will be detected.
(2) Number of words for slave station
Specify the data size of slace station in low byte in BCD.
The valid range is H00 to H48. If the value is more than H49 or including A to F characters, the iinitial setting
error will be detected.
Ex.) In case of station number 01(16 words), station number 14(4 words) and station number 29(32 words) make
data link.
1st word : H0116
2nd word : H1404
3rd word : H2932
With above configuration, data table is as follows.
(1)
1 word
(2)
St.00 (master)
St.01
St.14
St.29
WM0
WM8
WM18
WM1C
WM0 toWM7
WM8 to WM17
WM18 to WM1B
WM1C to WM3B