Chapter 6 Communication Mode
6 - 34
Mod
b
u
s M
a
ster
(2) Sample program description
The s parameter and the parameter of sending data area are set upon first scan.
TRNS 9 will be performed at 2nd scan (falling of R7E3), the following initial setting is configured on port 2
mounted on slot 2 of unit 3.
Items
Setup value
Setup contents
Communication mode
H0010
Modbus master mode
Modbus transmission mode
H0000
RTU mode
Receiving timeout time
50
500 ms
« Note »
TRNS 9 is initialized at the 1st scan. So other settings and operations should be executed after the 2nd scan.
Initial setting and communication are operated by TRNS command. However, do not use TRNS command twice
or more for one port. So each setting must be configured by one TRNS command with different parameter tables.