7 - 1
Chapter 7
System setup
7.1
Trial Run
Check item
Please check the item of Table 7.1.
Table 7.1 Check item at the time of a trial run
No.
Item
Contents
1
Modules except EH-SIO
Is wiring of a power supply etc. right?
Do the type & version of CPU module correspond to EH-SIO?
Is the ladder program download to CPU module?
2
Module mounting
Is mechanical connection good?
Is the attachment position of EH-SIO on the basic base or the expansion base?
3
Set up of communication setting
switch
Is it correct operation mode?
(Transmission speed, Transmission format configuration, Communication I/F
of port2)
4
Connection with external device
Is a communication cable correct connection?
Is mechanical connection good?
The procedure of trial run
Figure 7.1 Flow of the trial RUN
Please check whether it is set up correctly about transmission
speed, transmission format configuration, and communication
I/F of port 2.
Please check the state display LED of EH-SIO.
«The state at the time of the power supply ON »
Please check that RUN LED of CPU module is lighting.
Please check that LED which shows the setup communication
mode is on.
Please check whether EH-SIO can communicate.
Please check whether it becomes intentioned operation.
Communication mode LED -- Lighting
Error LED
-- OFF
* “422” LED depends on port setting.
Check of the communication setting
switch
Power supply ON
CPU is RUN
Initial setting of EH-SIO is executed
by TRNS 9.
Operation is checked by the easy
communication program.
An actual program is transmitted.
Trial RUN
SERIAL I/O
EH-SIO
MDE CDE
SD2 RD2
WDE
MB
1
HP1 MB
2
HP2
MS
1
422
1
MS
2
422
2
SD1 RD1
LNK
Содержание EH-150 Series
Страница 1: ...HITACHI PROGRAMMABLE CONTROLLER Serial Communication Module EH SIO APPLICATION MANUAL NJI 443F X ...
Страница 2: ......
Страница 10: ...M E M O ...
Страница 30: ...Chapter 4 Installation 4 10 M E M O ...
Страница 156: ...Chapter 7 System setup 7 12 M E M O ...
Страница 164: ...Chapter 8 Daily and Periodic Inspection 8 8 M E M O ...