26
5.7 Fault diagnostics
Fault
Cause
Remedy
Fan motor does not start
No power detectable
- Check wiring
Burner control is defect
- Replace burner control
Fan is defect
- Replace fan
Signal for stage 1 is off
- Check temperature setting at the boiler thermostat
- Check wiring between burner
and boiler control
- Check function of the gas-air system
Fan is running; fault occurs during
Flame appears during pre-purge
- Check wiring of the solenoid valves
pre-purge
- Check ionisation electrode (connection to ground)
Blower is running; fault occurs during
Ionisation electrode is defect
- Replace electrode bloc with cable
safety time
Ionisation current is too low
- Check position of the ionisation electrode
- Improve combustion
(increase/decrease gas volume flow)
Cable of the ionisation electrode is defect
- Replace electrode bloc with cable
Missing protective ground between
- Check wiring. To provide power supply, the burner
control box and burner casing
must be connected to phase, neutral and
protective ground.
No flame
- Non-ignitable mixture. Check setting of gas-air
system and the fan speed.
- Surface load (burner performance) is too low. Check
setting on gas-air system and check fan speed.
Gas-air system defect
- Replace gas-air system
Shutoff valve of gas pipe is closed
- Open shutoff valve
No ignition spark
Ignition unit is defect
- Replace ignition unit
Ignition electrodes are defect
- Replace electrode bloc with cable
Ignition cables are defect
- Replace electrode bloc with cable
Electrodes positioned incorrectly
- Align electrodes according to fig. 10
Fault on burner cannot be eliminated;
Burner control is defect
- Replace burner control
blower runs with maximum speed
Fan is defect
- Replace fan
Speed control/signal generator is defect
- Replace speed control/signal generator
Wiring between speed control/signal generator
- Check wiring, if necessary replace cable
and fan is defect
Содержание HG 30
Страница 16: ...15 St rursachendiagnose Lock out diagnoses Diagnostic des mises en d rangement...
Страница 18: ...17 5 2 Schaltplan 2 stufiger Brenner Circuit diagramm 2 stage burner Sch ma de connexions br leur deux allures...
Страница 20: ...19 19 5 4 Abmessungen Dimensions Dimensions HG Z M 30s...
Страница 21: ...20 5 4 Abmessungen Dimensions Dimensions HG Z M 30s...
Страница 22: ...21 21 5 5 Ersatzteilzeichnung Spare part drawing Vue clat e des pi ces de rechange HG Z M 30s...