14.09.2020
39 / 156
VARMAX -
Installation, Use and Maintenance
4.12.6. Boiler with 2 or 3 tappings
2 tappings
If all the circuits have the same return temperatures,
the return tapping located in the lower part must
be used.
U0501961-A
Flow
figure 27 -
Connection with 2 tappings
Clamp obstructing
2
nd
return
Return
3 tappings
VARMAX boilers are fitted with 2 returns and an
optimised internal water circuit allowing effective
separation of high temperature returns (coming
from DHW preparation circuits, radiators, etc.)
from low temperature circuits (underfloor heating
circuits, low temperature radiator circuits, etc.).
This circuit separation encourages the
condensation of flue-gases in the lower part of
the condenser throughout the year, and therefore
considerably increases the boiler's performance.
To use the 2
nd
return, the clamp obstructing the
tapping must be removed.
U0501961-A
figure 28 -
Connection with 3 tappings
Flow
2
nd
return
hot return (high temperature
circuit)
1
st
return
cold return (underfloor
heating and low
temperature radiators)
Содержание VARMAX 120
Страница 11: ...14 09 2020 11 156 VARMAX Installation Use and Maintenance ...
Страница 44: ...44 156 00BNO9168 I U0606551 VARMAX Installation Use and Maintenance figure 33 Electrical wiring diagram ...
Страница 125: ...14 09 2020 125 156 VARMAX Installation Use and Maintenance ...
Страница 155: ...14 09 2020 155 156 VARMAX Installation Use and Maintenance ...