14.09.2020
73 / 156
VARMAX -
Installation, Use and Maintenance
Line No. Value
Diagram VX112 only:
Define a low level
Input function H1 (5950)
Circulation circuit
demand 1
Install a shunt on H1
OR
reverse
the direction of contact
Type of contact (5951)
Rest contact
For the DHW to be effective, it is
necessary to define a trigger, even
if it is not connected.
Output via relay QX2 (5891)
Pump/valve ECS
Q3
Configure the extension modules
Function of extension module 1 (6020)
Heating circuit 1
Function of extension module 2 (6021)
Heating circuit 2
Function of extension module 3 (6022)
Heating circuit 3
• Heating circuit 1 / 2 / 3
menu
For each circuit
Set the comfort setting
Temperature of comfort setting (710/1010/1310)
- - -
Set the curve slope
Slope of the heating curve(720/1020/1320)
- - -
• Switch the heating mode to permanent comfort
Diagram VX112 only:
• Circulation circuit 1
menu
Set the starting value to use in
the event of a demand from the
circulation circuit
Starting value in case of circuit demand
(1859)
60°C (depends on
Rubis setting)
• Domestic hot water
menu
Set the comfort setting
Comfort setpoint
(1610) 55 °C
Set the DHW release mode
DHW release (1620) 24/7
• Activate DHW mode
Diagrams: VX102 / VX112
page 4 / 6
Содержание VARMAX 120
Страница 11: ...14 09 2020 11 156 VARMAX Installation Use and Maintenance ...
Страница 44: ...44 156 00BNO9168 I U0606551 VARMAX Installation Use and Maintenance figure 33 Electrical wiring diagram ...
Страница 125: ...14 09 2020 125 156 VARMAX Installation Use and Maintenance ...
Страница 155: ...14 09 2020 155 156 VARMAX Installation Use and Maintenance ...