Installation, Use and Maintenance
The flue-gas terminal's installation must comply with rules in §
4.11.
Ensure the slope towards the boiler is at least 3° (flue-gas side). On the air
duct side, adjust a slope to the outside to avoid the risk of rainwater in the
boiler.
To facilitate mounting flue-gas ducts for models 120 to 225, coat the joints in
liquid soap or a suitable grease (provided in the "terminal kit").
figure 25 - Type C53 connection (VARMAX
models 120 to 225)
figure 26 - Type C53 connection (VARMAX
models 275 to 600)
IMPORTANT:
The weight of flue-gas ducts must not be supported by the boiler.
U0501496-#
U0501350-#
L2
L1
L1
L2
ø
F
ø
A
ø
F
ø
A
450 mm
maxi
450 mm
maxi
450 mm
maxi
450 mm
maxi