VARMAX -
Installation, Use and Maintenance
Diagrams: VX210 / VX220
page 5 / 8
Line No. Value
Diagram VX210 only:
• Domestic hot water
menu
Set the comfort setting
Comfort setpoint
(1610) - - -
• Activate DHW mode
Diagram VX220 only:
• Circulation circuit 1
menu
Set the starting value to use in the event of
a demand from the circulation circuit
Value of starting temperature for
circulation circuit demand (1859)
- - -
On boiler(s) No. 2 (and later): slave
•
Configure as slave in the cascade:
LPB network
menu
Appliance number
Appliance address (6600)
2 (or later for the
other slaves)
Segment number
Segment address (6601)
0
Set the bus power supply.
Bus supply function (6604)
Automatic
Set the clock mode
Clock function (6640)
Slave without
adjustment
• Connect the bus between the boilers ( respect the polarity).
•
Turn off the slave boiler(s) and then turn on again. If communication is successful, the clock is
correctly updated.
E. ELECTRICAL AND HYDRAULIC VALIDATION
On boiler No. 1: master
• Cascade diagnostic
menu
Check that all boilers are present in the cascade
Status of generator 1 (8100)
Released / not
released
Status of generator 2 (8101)
Released / not
released
Содержание VARMAX 120
Страница 11: ...14 09 2020 11 156 VARMAX Installation Use and Maintenance ...
Страница 44: ...44 156 00BNO9168 I U0606551 VARMAX Installation Use and Maintenance figure 33 Electrical wiring diagram ...
Страница 125: ...14 09 2020 125 156 VARMAX Installation Use and Maintenance ...
Страница 155: ...14 09 2020 155 156 VARMAX Installation Use and Maintenance ...