VARMAX -
Installation, Use and Maintenance
9.4.3.
Controlling a Q2, Q6 or Q20 heating circuit pump
D. SPECIFIC START-UP PROCEDURE
Line No. Value
• Configuration
menu
Case of a 0-10V command Q2, Q6 or
Q20 heating pump. Configure the heating
pump.
Function output Ux (6078/6089)
Heat circuit pump
HC1 Q2
Or
Heat circuit pump
HC2 Q6
Or
Heat circuit pump
HC3 Q20
Signal direction.
Progress of the 0-10V signal in the signal
increase direction for speed increase.
Signal logil output UX (6079/6090)
Standard
• Heating circuit 1/2/3
menu
Set these 3 parameters to the same value
Starting speed (881/1181/1481)
between 0 and 100 %
Pump speed min (882/1182/1482)
between 0 and 100 %
Pump speed max (883/1183/1483)
between 0 and 100 %
E. ELECTRICAL AND HYDRAULIC VALIDATION
Line No. Value
• Input/output test
menu
Check the outputs
Pump with 0-10 V control
Output test Ux (7716/7724)
in V
9.4.4.
Controlling a DHW pump Q3
D. SPECIFIC START-UP PROCEDURE
Line No. Value
• Configuration
menu
Case of a 0-10V command DHW pump.
Configure the DHW pump Q3.
Function output Ux (6078/6089)
Pompe ECS Q3
Signal direction.
Progress of the 0-10V signal in the signal
increase direction for speed increase.
Signal logil output UX (6079/6090)
Standard
Содержание VARMAX 120
Страница 11: ...14 09 2020 11 156 VARMAX Installation Use and Maintenance ...
Страница 44: ...44 156 00BNO9168 I U0606551 VARMAX Installation Use and Maintenance figure 33 Electrical wiring diagram ...
Страница 125: ...14 09 2020 125 156 VARMAX Installation Use and Maintenance ...
Страница 155: ...14 09 2020 155 156 VARMAX Installation Use and Maintenance ...