92 / 156
00BNO9168-I (U0606551)
VARMAX -
Installation, Use and Maintenance
Line No. Value
Check sensor values
External sensor B9
External T° B9 (7730)
in °C
Flow sensor B1
Temperature sensor BX21 module 1 (7830)
in °C
F. OPTIMISATION OF SETTINGS
Line No. Value
• Heating circuit 1
menu
Set the reduced setting
Reduced temperature setting (712)
- - -
• HC1 time programme
menu
Preselection
Preselection (500)
- - -
Adjust the time programme
On / Off phases (501...506)
- - -
• Circuit HC1 holiday
menu
Preselection
Preselection (641)
- - -
Adjust the time programme
On / Off phases (642-643)
- - -
Diagram VX120
page 4 / 4
• Switch the heating mode to automatic
AUTO
• Configuration
menu
Activate the heating circuits' frost
protection mode
Frost protection plant (6120)
On
Maintenance optimisation:
It is possible to generate a maintenance message without harming the boiler. This maintenance
message may appear when the 3 following meters have elapsed:
• Time since last maintenance (or commissioning): set parameter 7044 to 12 months
• Operating hours of the burner (parameter 7040)
• Number of start-ups (parameter 7042)
The last 2 parameters depend on the boiler room's hydraulic installation. It is recommended to
use at least parameter 7044 for yearly maintenance.
Содержание VARMAX 120
Страница 11: ...14 09 2020 11 156 VARMAX Installation Use and Maintenance ...
Страница 44: ...44 156 00BNO9168 I U0606551 VARMAX Installation Use and Maintenance figure 33 Electrical wiring diagram ...
Страница 125: ...14 09 2020 125 156 VARMAX Installation Use and Maintenance ...
Страница 155: ...14 09 2020 155 156 VARMAX Installation Use and Maintenance ...