144 / 156
00BNO9168-I (U0606551)
VARMAX -
Installation, Use and Maintenance
Line
No.
Programme
Access
Default value
Customer setting
Consumer circuit 1
1859
Flow temp setp cons request
C
60 °C
1875
Excess heat draw
S
On
1878
With buffer
S
No
1880
With prim contr/system pump
S
No
Consumer circuit 2
1909
Flow temp setp cons request
C
60 °C
1925
Excess heat draw
S
On
1928
With buffer
S
No
1930
With prim contr/system pump
S
No
Consumer circuit 3
1959
Flow temp setp cons request
C
70 °C
1975
Excess heat draw
S
On
1978
With buffer
S
No
1980
With prim contr/system pump
S
No
Swimming pool
2055
Setpoint solar heating
S
26 °C
2056
Setpoint source heating
S
22 °C
2065
Charging priority solar
S
Priority 2
2080
With solar integration
S
Yes
Boiler
2203
Release below outside temp
S
0 °C
2208
Full charging buffer
S
Off
2210
Setpoint min
S
8 °C
2212
Setpoint max
S
85 °C
2214
Setpoint manual control
E
70 °C
2217
Setpoint frost protection
S
8°C
2243
Burner off time min
S
5 min
2250
Pump overrun time
S
5 min
2253
Pump overr time after DHW
S
1 min
2270
Return setpoint min
S
8 °C
2321
Starting speed
S
100 %
2322
Pump speed min
S
100 %
2323
Pump speed max
S
100 %
2330
Output nominal
S
Depending on boiler
2331
Output basic stage
S
Depending on boiler
2334
Output at pump speed min
S
0 %
2335
Output at pump speed max
S
100 %
2441
Fan speed heating max
S
Depending on boiler
2442
Fan speed full charging max
S
Depending on boiler
2444
Fan speed DHW max
S
Depending on boiler
2454
Switching diff on HCs
S
3 °C
2455
Switching diff off min HCs
S
3 °C
2456
Switching diff off max HCs
S
6 °C
2457
Settling time HCs
S
20 min
2460
Switching diff on DHW
S
3 °C
2461
Switching diff off min DHW
S
3 °C
2462
Switching diff off max DHW
S
6 °C
2463
Settling time DHW
S
20 min
Содержание VARMAX 120
Страница 11: ...14 09 2020 11 156 VARMAX Installation Use and Maintenance ...
Страница 44: ...44 156 00BNO9168 I U0606551 VARMAX Installation Use and Maintenance figure 33 Electrical wiring diagram ...
Страница 125: ...14 09 2020 125 156 VARMAX Installation Use and Maintenance ...
Страница 155: ...14 09 2020 155 156 VARMAX Installation Use and Maintenance ...