118 / 156
00BNO9168-I (U0606551)
VARMAX -
Installation, Use and Maintenance
Line No. Value
Diagram VX212 only:
• Circulation circuit 1
menu
Set the starting value to use in
the event of a demand from the
circulation circuit
Starting value in case of circuit demand
(1859)
60°C (depends on
Rubis setting)
• Domestic hot water
menu
Set the comfort setting
Comfort setpoint
(1610) 55 °C
Set the DHW release mode
DHW release (1620) 24/7
• Activate DHW mode
On boiler(s) No. 2 (and later): slave
• Configuration
menu
If there is a 4th heating circuit:
Start up
the heating circuit 1
Heating circuit 1 (5710)
On
Configure the extension module
Function of extension module 1 (6020)
Heating circuit 1
•
Configure as slave in the cascade:
LPB network
menu
Appliance number
Appliance address (6600)
2 (or later for the
other slaves)
Segment number
Segment address (6601)
0
Set the bus power supply.
Bus supply function (6604)
Automatic
Set the clock mode
Clock function (6640)
Slave without
adjustment
If there is a 4th heating circuit:
• Set the heating circuit:
Heating circuit 1
menu
Set the comfort setting
Comfort setting temperature (710)
- - -
Set the curve slope
Heating curve slope (720)
- - -
• Switch the heating mode to permanent comfort
• Connect the bus between the boilers ( respect the polarity).
•
Turn off the slave boiler(s) and then turn on again. If communication is successful, the clock is
correctly updated.
Diagrams: VX202 / VX212
page 6 / 9
Содержание VARMAX 120
Страница 11: ...14 09 2020 11 156 VARMAX Installation Use and Maintenance ...
Страница 44: ...44 156 00BNO9168 I U0606551 VARMAX Installation Use and Maintenance figure 33 Electrical wiring diagram ...
Страница 125: ...14 09 2020 125 156 VARMAX Installation Use and Maintenance ...
Страница 155: ...14 09 2020 155 156 VARMAX Installation Use and Maintenance ...