125
[28, 29] High/low pressure sensor failure
Reconnect
If sensor terminal is fixed well
If voltage between red
terminal and black terminal is 5V
when testing pressure sensor by
multimeter
If voltage between white terminal and
black terminal is 0.5V~3.5V when
testing pressure sensor
by multimeter
Replace connecting board
Replace PCB
Replace pressure sensor
N
Y
Y
N
N
Y
Содержание HU062WAMNA
Страница 1: ...ATW Split Service Manual SYJS 2022 A Edition 2022 A ...
Страница 16: ...16 6 Piping Diagram ...
Страница 25: ...25 Cooling Tao C Two C Ta Ambient temperature Two Outlet water temperature ...